DiTemp ATTS
The DiTemp ATTS is an automatic test and trigger system that verifies a distributed temperature sensing (DiTemp) installation by simulating heating or cooling events at both ends of the sensing cable. It logs detection timing so operators can confirm the system's alert response and Safety Integrity Level (SIL) performance over time.
- Hot/cold spot size
- 2 m
- Number of hot/cold spots
- 2
- Maximum temperature change
- ±15°C / 10 s

Overview
In detail
How it works
Two ~2 m sections of optical fiber, placed at the beginning and end of the real sensing cable, are heated or cooled in a controlled, repeatable way to reproduce the temperature signature of an anomaly such as a leak. Simulated events are typically generated every hour. The DiTemp ATTS records the timing of each simulation start and the alert it triggers in a dedicated test zone of a DiTemp Relay Module, controlled by the DiView software. If no alert arrives within a preset timeout, the ATTS itself raises an alert flagging that the monitoring system may be unavailable.
Because the simulated events occupy their own dedicated zone, real leakages are still detected during a test, and alerts from the test zone are not passed on to the plant controller or allowed to trigger any control action.
Reporting
The system records every timing result so a report can be generated periodically, summarizing the availability score and the average and maximum reaction times. This gives an ongoing, evidence-based evaluation of the installation's SIL (Safety Integrity Level proven by experience) rating.
Reach out and say hi
Let us help. Tell us the site, the range you expect and what it has to talk to, and we’ll work out the right variant, cable and mounting — and quote it.
Specifications
Technical specifications
- Hot/cold spot size
- 2 m
- Number of hot/cold spots
- 2
- Maximum temperature change
- ±15°C / 10 s
- Heat/cool period
- 10 s to 5 minutes (factory set)
- Heat/cool cycle
- 1 minute to 24 h (factory set)
- Modes of operation
- Heat or cool (factory set)
- Fiber typology
- MMF 50/125 µm (ITU-T G.651)
- Memory size
- 2 years at 1 h cycle time
- Operating temperature
- 5°C to 40°C
- Storage temperature
- -15°C to +65°C
- Humidity
- 5% to 95% RH, non-condensing